TRE ELCB

1.Small size, high capacity;

2.Rated current have fixed type and adjustable type(0.8In-1.0In);

3.Modular structure design, better performance;

4.Ics=100% Icu;

Service hotline
0577-8801 9159

TRE series circuit breakers and auxiliaries comply with the following international standard:

IEC/EN 60947-1: Low-voltage switchgear and controlgear-Part 1: General rules

IEC/EN 60947-2: Low-voltage switchgear and controlgear-Part 2: Circuit breakers


TRE series ELCB(Standard use environment for TRE series ELCB)
1. Ambient temperature: Within the range of -5ºC--+40ºC(However, the average for the duration of 24 hours must not exceed 35ºC);
2. Altitude: 2000m or less
3. Installation class: III
4. The magnetic field near the instalation site should not be more than five times the earth magnetic field in any direction.
5. Pollution: II


Classification:
According to the poles:                                        2-poles, 3-poles
According to the breaking capacity:                       S-type, H-type
According to the rated current:                             Fix type, Adjustable type(08In-1.0In)
According to the trip action time:                           Fix type, Adjustable type(0.1s/0.3s/0.5s or 0.45s/1.0s/2.0s)
According to the rated residual current:                 Fix type, Adjustable type(30mA/100mA/300mA/500mA)

Frame sizeTREF1 (63A)
Breaking capacity codeSH
Type and pole2P3P2P3P
TREF1-S2TREF1-S3TREF1-H2TREF1-H3
Protective functionOverload & Short-circuit & Ground fault
Rated current ,In (A)15A, 20A, 30A, 40A, 50A, 63A
Rated residual currentOperating ,IΔn (mA)30mA, 50mA,100mA,200mA,300mA,500mA
Non-operating ,IΔno (mA)15mA,25mA,50mA,100mA,150mA,250mA
Adjustable partRated current setting(0.8In~1.0In)
Lockup device for operating handle--
Residual current setting, IΔn30mA / 100mA / 300mA / 500mA
Trip action time setting0.1s / 0.3s / 0.5s
Rated operational voltage ,Ue (V) ,AC 50/60 Hz240V/415V
Rated insulation voltage ,Ui (V)1000V
Rated impulse withstand voltage ,Uimp (KV)8kV
Residual current off-time at IΔn ,Sec (s)0.1s
StandardConformity with IEC / EN 60947-2
Rated frequency (Hz)50/60 Hz
Rated short-circuit breaking capacity ,Icu (KA)
AC240V14kA25kA
415V5kA7.5kA
Ics=%*Icu100%
Mechanical life (circle)8500
Electrical life (circle)1500
Dimension
Length*Width*Height(mm)
2-pole100mm*50mm*60mm
3-pole100mm*75mm*60mm
4-pole-

Built-in accessory:

Built-out accessory: