TRM series circuit breakers and auxiliaries comply with the following international standard:
IEC/EN 60947-1: Low-voltage switchgear and controlgear-Part 1: General rules
IEC/EN 60947-2: Low-voltage switchgear and controlgear-Part 2: Circuit breakers
TRM series MCCB (Standard use environment for TRM series MCCB)
1. Ambient temperature: Within the range of -5ºC--+55ºC(However, when the temperature exceed 40ºC,it should be considered to reduce the capacity to use);
2. Relative humidity: Within the range of 45%--85%;
3. Altitude: 2000m or less(However, if it exceeds 1000m, atmosphere correction through humidity test and withstand voltage test can be considered);
4. Atmosphere where excessive steam, oil steam, smoke, dust, salt and other corrosive materials do not exist;
Classification:
According to the poles: 1-pole, 3-poles, 4-poles
According to the breaking capacity: S-type, H-type
According to the rated current: Fix type, Adjustable type(08In-1.0In)
Frame size | TRMF4(250A) | ||||||
Breaking capacity code | S | H | |||||
Product code and pole | 1P | 3P | 4P | 1P | 3P | 4P | |
TRMF4-S1 | TRMF4-S3 | TRMF4-S4 | TRMF4-H1 | TRMF4-H3 | TRMF4-H4 | ||
Rated current,In(A) | 100A, 125A, 160A, 180A, 200A, 225A, 250A | ||||||
Adjustable part | Rated current setting(0.8In~1.0In) | X | √ | √ | X | √ | √ |
Lockup device for operating handle | X | √ | √ | X | √ | √ | |
Rated operational voltage,Ue(V),AC50/60Hz | 240V/415V | ||||||
Rated insulation voltage,Ui(V) | 1000V | ||||||
Rated impulse withstand voltage,Uimp(kV) | 8kV | ||||||
Standard | Conformity with IEC/EN 60947-2 | ||||||
Rated frequency(Hz) | 50/60Hz | ||||||
Rated short-circuit breaking capacity,Icu(kA) | |||||||
AC | 240V | 25kA | 50kA | 36kA | 65kA | ||
415V | - | 37kA | - | 50kA | |||
Ics=%*Icu | 50% | 100% | 50% | 100% | |||
Mechanical life(circle) | 7000 | ||||||
Electrical life(circle) | 1000 | ||||||
Dimension Length*Width*Height(mm)
| 1-pole | 150mm*38mm*60mm | |||||
2-poles | - | ||||||
3-poles | 165mm*105mm*60mm | ||||||
4-poles | 165mm*140mm*60mm |